5 feedback systems, Installation – Lenze EDS4900U-REG User Manual

Page 59

Advertising
background image

Installation

4-21

48XX/49XXSHB0399

4.3.5

Feedback systems

Several feedback systems can be connected to the controller and configured:

( Armature voltage control
( DC tacho feedback
( Resolver feedback
( Encoder feedback

- Incremental encoder TTL

- Incremental encoder HTL

DC tacho feedback

Tacho signals are connected via term. 3/4 of terminal block X1. The controller
processes rated tacho voltages of 10...180V (chapter 4.3.5.1).

Resolver feedback (X7)

( 2-pole resolver (V = 10 V, f = 5 kHz)
( Connection to a 9-pole Sub D socket X7

- We recommend to use the pre-cut Lenze system cable

(see chapter 13.3).

( Resolver cable and resolver are monitored for wire breakage (fault message

”Sd2”)

+ REF

-REF

+ COS

-COS

+ SIN

-SIN

1

2

3

4

5

6

7

8

9

X7

lmax= 50 m

4900Str015

FIG 4-15

Resolver connection (9-pole Sub D socket)

Pin assignment of socket X7:

Pin

1

2

3

4

5

6

7

8

9

Signal

+ REF

-REF

GND

+ COS

-COS

+ SIN

-SIN

---

---

Cross section

0.5

0.14

Show/Hide Bookmarks