Commissioning

5-3

48XX/49XXSHB0399

The following table describes briefly how to commission a DC shunt motor with an
attached tacho according to the example in FIG 5-1(see chapter 15).

Section

Activity

see also

Switch-on sequence 1.X2/28 (Ctrl. enable) must be opened (LOW)

2.Connect the mains

Approx. 0.5sec after mains connection the
controller is ready for operation.
The time t

1

depends on the initial response

of the field current

Typical values:

t

1

= 300ms ...600ms

t

2

= t

1

+ 20ms

FIG: Signal flow after mains connection
(see fig. on the right)

50 ms

TRIP

RDY

t

t

1

2

Mains on

Integration of the
armature controller
in its operating point

Controller
enable

field

I

90 % of the
rated current

Time

Armature
current

4900Str025

Input of the
motor data

3.Input of the motor nameplate data

- C083

Rated field current

- C084

Armature circuit time constant

- C088

Rated motor current

- C090

Rated motor voltage

Chapter 5.2

adaptation of tacho

4.Set S4 before adapting the tacho voltage

Chapter 7.1.2.2

p

constants

- C025

-2- Select adjustment of terminals 3, 4

- C029

Adjustment of actual speed

p

Set the current limit 5.Max. motor current

- C022

+ I

Amax

- C023

-I

Amax

Adjustment of max.
speed

6.Select the reference value for 100% setpoint

- C011

max. speed

Select direction of
rotation

7.CW rotation:

HIGH signal at X2/21 (+ 13...+ 30 V)

CCW rotation: HIGH signal at X2/22 (+ 13...+ 30 V)

Chapter 5.4

Setpoint selection

8.Apply a voltage higher than 0V (max. 10V)

- do not achivate JOG setpoint (LOW signal at X2/E4 and X2/E5)

Check whether LED
’RDY’ ison

9.If RDY is off and C067 is blinking, remove TRIP first.

Chapter 8.1 ff.

Controller enable

10. Assign HIGH-signal to X2/28 (+ 13...+ 30 V) and do not press STP
The motor will now run with the selected setpoint and in the selected direction of rotation. If
necessary, adapt the controller to your application.

Chapter 5.3

Additional settings

11. Further setting required for LECOM operation

Stop!

( Do not change the switch-off sequence

The controller must only be disconnected from the mains when it is inhibited or the
motor is in standstill (for mains switch-off logic see chapter 15.9.2).