Connection of digital signals

( All digital inputs and outputs are PLC compatible and separated from the

rest of the control module when operated with an external voltage supply
(24 V).

( The diagrams show the function assignments according to the factory

setting.

( For switching the signal cables, only relays with contacts for low-level

switching should be used.
We recommend using relays with gold contacts.

( Voltage supply

- external 24 V to terminals X2/39 and X4/59 or

- internal 15 V to terminal X2/20

Stop!

( Maximum permissible load of the internal 15 V supply : 100 mA.
( For operation with internal voltage: Bridge terminals X2/39 and X3/40

externally.

( Digital inputs unused should be connected!

Inputs:

Input voltage

0

...

+ 30 V

LOW level:

0

...

+ 5 V

HIGH level:

+ 13

...

+ 30 V

Input current:

24 V:
15 V:

8 mA per input
5 mA per input

Outputs:

Output current:

Max. 50 mA per output
(external resistance min. 480

W at 24V,

e. g. relay, order designation EK0005)

The input and output signals are in average read, processed and updated every
4 msec on average.