7-42

48XX/49XXSHB0399

QSP at the master

If QSP is switched at the master drive, the set-value (C050) is reduced along the
QSP ramp for all drives. Thus, the complete network of drives can be decelerated
to standstill by the QSP integrator.
If QSP is reset before standstill is achieved, the network of drives starts to
accelerate or decelerate at the set-value integrator with the value set under C050.

QSP at slave 0 (master drive)

If the deceleration ramp is very short and it can only be achieved with I

max

, the

phase synchronism will be lost. With the I

max

message, the set-value integrator

follows the actual phase integrator. Thus, the rotor does not turn back when
reaching n = 0. If the I

max

message is reset, the phase control will be reactivated

and drift-free standstill can be ensured.
The switching of QSP is a continuous operating mode for the connected slaves
so that a reversal is possible, if the deceleration ramp set at the master should be
too short for one of the slaves.

Ctrl. enable at the master

If the master is inhibited, the actual value of slave 0 is used as a set-value for the
other slaves.Thus, the complete network of drives could be decelerated to
standstill by the coasting slave 0.
If the master is enabled before standstill, the network of drives starts to accelerate
with the actual speed at the set-value integrator.

The phase difference is set to zero by switching controller enable.

7.3.2

Slave for digital frequency bar

Purpose

With configuration C005 = -62- or -63- for the set-value bar,

( the phase control, which is preconnected to the speed controller, is

activated and

( the set-value path is changed to digital frequency coupling for phase and

speed synchronous running.