Configuration – Lenze EDS4900U-REG User Manual

Page 218

Advertising
background image

Configuration

7-127

48XX/49XXSHB0399

Code

Possible settings

Name

Code

Info

Selection

Lenze

Name

C069

Controller state

Bit

Meaning

0

Operation error

1

Communication error

2

Operating mode was changed

3

Control via LECOM active

4

Control via terminals active

5

Controller reset (CCr fault)

6

not assigned

7

Controller enable

8 bit status information
Only readable via LECOM. The signals are
described in the LECOM-A/B protocol.

C070

V

pn

of the speed

controller

8

1

{1}

1000

Gain adjustment of the speed controller:
1.With low motor speed, increase V

pn

until

the drive starts to oscillate (high
frequency).

2.Reduce V

pn

, until the drive runs

smoothly.

[C071*] T

nn

of the speed

controller

400 ms 20 ms

{10 ms}

2000 ms
9999 ms

Integral action time of the speed controller
T

nn

= 9999 ms: I-component switched-off

(only when controller is inhibited)

C072*

K

dn

of the speed

controller

0

0

¼V

pn

{0.1}

5.0

¼V

pn

Differential component of the speed
controller

C077*

V

pl

of the field

controller

1.0

0.1

{0.1}

5.0

Gain adjustment of the field controller

C078*

T

nl

of the field

controller

300 ms 70 ms

{10 ms}

2000 ms

Integral action time of the field controller

C079*

PT1 element
Time constant
for field
controller
attenuation

140 ms 30 ms

{10 ms}

9000 ms

The larger the time constant, the larger
the decoupling between armature and
field circuits.

C081*

Rated motor
power

6.7 kW 0.0 kW

{0.1 kW}

10.0 kW

10kW

{1kW}

1000kW

See motor nameplate

C083

¤ Rated field

current

0A

0 A

{0.01 A}

30.0 A

Rated current depends on the controller:
0A/0.1A ... 3.5A

(4902, 4903)

0A/0.3A ... 10A

(4904 - 4907)

0A/0.3A ... 15A

(4X08)

0A/0.3A ... 30A

(4X09 - 4X13)

Data on the motor nameplate are
setpoints for the field current. With very
low field currents an auxiliary starting
circuit should be provided.

C084*

¤ CW/CCW

armature time
constant

10 ms

0 ms

{5 ms}

30 ms

Adaption of the current controller to
compensated and uncompensated motors
0 ms = adaption not active

C085*

¤ Thermal motor

time constant

1.0min 1.0 min

{0.1 min}

100.0 min

Required for ”I

2

¼

t monitoring” (motor

protection)

C087

¤ Rated motor

speed

3000

rpm

300 rpm

{1 rpm}

5000 rpm

See motor nameplate