Configuration – Lenze EDS4900U-REG User Manual

Page 121

Advertising
background image

Configuration

7-30

48XX/49XXSHB0399

Normalization of digital frequency inputs

If the digital frequency inputs X5 and X9 are not assigned to the function setpoint
or act. value encoder - depending on the configuration - they can be assigned to
a function according to the selection under C146.

The input frequency is normalized via C026, C027 and C028.

Procedure:

1. Depending on the max. input frequency:

Selection C026

corresponds to incr./rev.

f

input

[kHz]

-5-

256

< 60

-4-

512

< 120

-3-

1024

< 240

-2-

2048

> 240

2. Numerator and denominator of the normalization factor:

( Numerator = 1024 / 2

(C026)

- For (C026): Enter the section number (see table above)

( Denominator = Input frequency [kHz];

The value entered corresponds to 100% setpoint

3. Detection of C027 and C028:

Divide numerator and denominator of the normalization factor by a adaptation
factor for both to get setting values for C027 and C028 in a range that is accepted
by the controller.

Example:

Max. input frequency = 9 kHz

1. C026 = -5- (256 incr./rev.)

2. Normalization factor:

( Numerator = 1024 / 2

5

= 32.0;

( Denominator = 9.0
3. Adaptation factor = 10; setting value C027 = 3.2; setting value C028 =

0.9

The adaptation factor should be as low as possible because of the internal
resolution.

Show/Hide Bookmarks