Configuration

7-117

48XX/49XXSHB0399

7.8.6

Display functions

Code set

The factory setting is the display of the standard code set.
The extended code set is displayed when selecting C000 = -2-.

Code

Name

Possible settings

Code

Name

Lenze Selection

Info

C000

¤

Code set

1

-0-

(+ PW) Standard code set read only

-1-

(+ PW) Standard code set

-2-

(+ PW) Extendend code set

-9-

For service only

-11-

Code set automation module

Can only be changed via keypad!
If a password is defined under C094, a
change from -0- to -1- or -2- is only
possible after entering this password
(+ PW):
1. Change C000,
acknowledge with

SH + PRG

.

2. Password setting with ▲ or ▼.
3. Accept with SH + PRG.

C094*

¤ User

password

0

0

{1}

999

0 = No password protection
(see also C000)

Language

Code

Name

Possible settings

Code

Name

Lenze Selection

Info

C098

Language

0

-0-

German

-1-

English

-2-

French

Actual value displays

Code

Name

Possible settings

Code

Name

Lenze Selection

Info

C051

n

act

speed

-5000 rpm

{1 rpm}

+ 5000 rpm

Display: actual speed

C052*

Motor
voltage

0 V

{1 V}

600 V

Display: motor voltage V

A

C054

Motor
current

0.0 A

0.1 A}

100 A

100 A

{1 A}

2000 A

Display: motor current I

A

C056

Torque
setpoint

-100.0 % M

max

{0.1 %}

+ 100.0 % M

max

Display: Torque setpoint
Armature setting range: 100% M

max

correspond to 100% I

max

(C022, C023)

C060*

Rotor
position

0...2047

Display: absolute rotor angle position,
standardized to 2048 incr./rev.
Incremental encoder feedback: display
only after zero track pulse.

C061*

I

¼t load

0.0 %

{0.1 %}

105.0%

Display: ”I

¼t load”. Starting value when

switching on the mains is always 100 % !

C185

P

motor

-500.0 kW

{0.1 kW}

500.0 kW

Display: actual motor power

C186

M

motor

-999 Nm

{1 Nm}

999 Nm

Display: actual motor torque

C187

I

Fset

0.00 A

{0.01 A}

50.0 A

Display: actual field current setpoint

C188

I

Fact

0.00 A

{0.01 A}

50.0 A

Display: actual field current value

C189

f

mains

0.0 Hz

{0.1 Hz}

100.0 Hz

Display: actual mains frequency