Installation – Lenze EDS4900U-REG User Manual

Page 54

Advertising
background image

Installation

4-16

48XX/49XXSHB0399

Analog outputs (monitor outputs)

Terminal

Switch position

Use

Level

Resolution

60

Internal ground, GND

61

Actual current value

-5 V...+ 5 V
correspond to the
rated current of the
controller

62

A

S2

Monitor 1
Output voltage(factory setting)

-10V...10V

11 bit

1

S2

Monitor 1
Output current

-20mA...+ 20mA

11 bit

63

A

S1

Monitor 2
Output voltage(factory setting)

-10V...+ 10V

11 bit

1

S1

Monitor 2
Output current

-20mA...+ 20mA

11 bit

1)

For changing the factory setting of switch S4, jumper 5 to ON (actual value with

ground reference), observe the following:

- Bridge terminals 4 and 5 externally.

- Set DIP switch S4, jumper 1-4 (preselected actual value) to double tacho

voltage.

The max. possible tacho voltage is 90 V!