4 freely assignable monitor outputs, Configuration, Stop – Lenze EDS4900U-REG User Manual

Page 124

Advertising
background image

Configuration

7-33

48XX/49XXSHB0399

7.1.5.4

Freely assignable monitor outputs

The controller is equipped with two analog (terminals 62 and 63) and a digital
(digital frequency output X8) monitor outputs to output internal signals as voltage,
current or frequency signals. The positions of switches S1 and S2 required for the
analog outputs, can be obtained from chapter 4.3.4.1.

If you want to assign a new signal to an output, select under C110 which output
is to be changed. Select under C111 the signal to be assigned to this output. Under
C108 and C09 adjust gain and offset (C109 is not valid for the digital frequency
output) to adapt the monitor output, for instance, to a display instrument.

Stop!

With freely assignable signals positive feedbacks may occur, which can lead to
uncontrolled drive acceleration!

Code

Name

Possible settings

Lenze Selection

Info

C108*

Gain for
C110

1.00

-10.000 {0.001} + 10.000

Gain for X4/62, X4/63, X8

C109*

Offset for
C110

0mV

-10000mV

{1mV}

+ 10000mV

Loading of the factory settings does not
overwrite C109.
Offset for X4/62, X4/63.
This code is only effective, if the digital
frequency output is selected under C110.

C110*

¤ Input

selection:
Monitor
output

1

-1-

Analog output X4/62 (monitor 1)

-2-

Analog output X4/63 (monitor 2)

-3-

Digital frequency output X8

The monitor outputs are freely assignable
with the signals under C111:
1.Select monitor output under C110.
2.Assign signals under C111.
3.If necessary, adjust under C108 and

C109.

Show/Hide Bookmarks