3 store parameter set, 4 load parameter set, Configuration – Lenze EDS4900U-REG User Manual

Page 205

Advertising
background image

Configuration

7-114

48XX/49XXSHB0399

7.8.4.3

Store parameter set

(see chapter 7.4.2)

The parameter must be stored to ensure that the setting will not be lost after mains
switching.

Up to four different parameter sets can be created, if, for instance, a machine
processes different materials or operates in different states (set-up, stand by, etc.).

If only one paramater set is required, store the change permanently under
parameter set 1, because this parameter set is automatically loaded after switch
on.

1. Select C003 usi ng

s or t .

2. Change to the parameter level using PRG.

3. Set the parameter to -1- using

s or t .

This is also possible during operation of the drive.

4. Press SH + PRG.

--ok-- is displayed for approx. 0.5 s.
Your settings are permanently stored under ”parameter set 1”.

7.8.4.4

Load parameter set

(see chapter 7.4.2)

Loading is only possible when the controller is inhibited.

Warning!

With the loading a new parameter set, the controller is initialised and operates as
if the mains had been switched.
User terminal X2/28 as source for the controller inhibit. Otherwise, the dirve can
start in an uncontrolled way when changing to another parameter set.

Main connection

The controller automatically loads parameter set 1.

Via keypad

1. Inhibit the controller via terminal 28.

2. Change to the parameter level using PRG.

3. Select C002 using

s or t .

4. Select a parameter set using

s or t .

5. Acknowledge with SH + PRG (--ok-- is displayed for approx. 0.5 s).

The parameter set selected is loaded. Enable the controller again.