5 freely assignable inputs and outputs, 1 freely assignable digital inputs (fdo), Configuration – Lenze EDS4900U-REG User Manual

Page 113

Advertising
background image

Configuration

7-22

48XX/49XXSHB0399

7.1.5

Freely assignable inputs and outputs

7.1.5.1

Freely assignable digital inputs (FDI)

Change of the function assignment

Proceed as follows to assign a new function to an input:

( Select the input to be assigned under code C112.
( Select the function required under code C113.
( Select under code C114 whether the function is to be activated with a HIGH

or a LOW signal.

( Determine under code C115 whether the function is always to be switched

via terminal or, depending on the operating mode, via the correspondingly
selected interface.

Code

Name

Possible settings

Lenze Selection

Info

C112*

¤ Input

selection:
Freely
assignable
digital input

1

-1-

digital input X2/E1

-2-

digital input X2/E2

...
-5-

digital input X2/E5

The digital inputs E1..E5 are freely
assignable with the functions under
C113.Each function can only be assigned
to one input.
Exceptions:
C113 = -20- : max. 2 dig. inputs
C113 = -1-, -2-, -40-: max. 4 dig. inputs
(binary coded selection of max. 1, 3, 7 or
15 additional T

i

times or set-values).

Assignment of functions:
1.Select input under C112.
2.Assign function under C113.
3.Determine polarity under C114.
4.Determine priority under C115.

[C113*] Function

for C112

-0-

No function

-1-

Enable additional T

i

times

-2-

Enable JOG set-value (X4/E4, E5)

-3-

TRIP reset (X2/E2)

-4-

TRIP set (X2/E1)

-6-

Switch-off additional setpoint (X4/E3)

-7-

Switch-off I-component of the n-controller

-9-

Ramp function generator stop

-10-

Ramp function generator zero

-16-

Motor potentiometer deactivated

-17-

Motor potentiometer down

-18-

Motor potentiometer up

-20-

Select parameter set

-21-

Load parameter set

-30-

Deactivate process controller

-31-

Switch-off I-component of the process
controller

-32-

Set process controller evaluation to 0

-40-

Enable fixed set-value

[C114*] Polarity for

C112

0

-0-

Input HIGH active

-1-

Input LOW active

Show/Hide Bookmarks