Configuration

7-111

48XX/49XXSHB0399

7.8.4

Basics for operation

7.8.4.1

Parameter change via a code

Note!

If changed parameter sets are required after mains switching, they must be stored
(chapter 7.8.4.3).

Each code with parameters, which can be changed, is factory set. Depending on
the code there are three possibilities to change a parameter.

Each possibilities is explained by means of an example.

Direct acceptance (on-line)

The controller accepts the changed parameter immediately.

1. Select a code using

s or t .

2. Change to the parameter level using PRG.

3. Select a parameter using

s or t .

The controller accepts the changed parameter immediately.
This is also possible during operation of the drive.

4. Change to the code level using PRG.

Code level

Parameter level

C

0

E

P

m

Code

Parameter

Un i t

0 1 1

r p m

0

0

3

N

a x

S

E D

PRG

C

0

E

P

m

C ode

Parameter

Un i t

0 1 1

r p m

0

0

3

N

a x

S

E D

Change a parameter
with

s or t

C

0

E

P

m

C ode

Parameter

Un i t

0 1 1

r p m

N

a x

S

E D

2 7 5

PRG

C

0

E

P

m

C ode

Parameter

Un i t

0 1 1

r p m

N

a x

S

E D

2 7 5