10 table of attributes, Configuration – Lenze EDS4900U-REG User Manual

Page 236

Advertising
background image

Configuration

7-145

48XX/49XXSHB0399

7.10

Table of attributes

The information given in this attribute table is required for generating a
programmme. It contains all information about the communication to the controller
via parameters:

Column

Meaning

Entry

Code

Name of the Lenze codes

Cxxxx

Index

dec

Index, under which the parameter
is defined.

24575

Lenze code

number

Is only required for control via
InterBus or PROFIBUS.

hex

The subindex of array variables
corresponds to the Lenze
subcode number.

5FFh

Lenze code

number

InterBus or PROFIBUS.

Data

DS

Data structure

E

Simple variable (one parameter value)

Data

DS

Data structure

A

Array variable (several parameter
elements can be selected through the
code for input selection or via LECOM
subcode)

I

Image variable (several parameter
elements can be selected through the
code for input selection).

DA

Number of array elements
(Subcodes)

xx

DT

Data type

B8

1 byte bit coded

DT

Data type

B16

2 byte bit coded

FIX32

32 bit value with sign; decimal with
four decimal codes
Example:
1 2

12000

FIX32 dec

1.2

12000

FIX32-dec

00002EEO

FIX32-hex

-10.45

-104500

FIX32-dec

FFFE67CC

FIX32-hex

I16

2 byte with sign
(-32768

$ X $ 32767)

I32

4 byte with sign
(-2147483648

$X $2147483647)

N16

16 bit value with sign
0%

0; 100% 2

14

Example:
100%

16384

N16-dec

4000

N16-hex

-50%

-8192

N16-dec

E000

N16-hex

U16

2 byte without sign
( 0

$X $ 65535)

VS

ASCII string

format

LECOM format

VD

ASCII decimal format

format

LECOM format
(see Operating Instructions for

VH

ASCII hexadecimal format

(see Operating Instructions for
fieldbus modules)

VS

String format

DL

Data length in byte

Access

P/S

Parameter setting / control

P

Parameter setting

Access

P/S

Parameter setting / control
(according to C001)

S

Control

LCM-R/W

Access authorization for LECOM

Ra

Reading is always permitted

LCM R/W

Access authorization for LECOM

Wa

Writing is always permitted

W

Writing depends on condition

AIF

Proceß datum in automation
interface
Mapping to LECOM2 process
data channel possible

PZD

Process datum

Show/Hide Bookmarks

Advertising