Configuration

7-116

48XX/49XXSHB0399

7.8.5

Operating modes

The controller can be adapted to your application in different ways:

Terminals:

The terminals are to control the controller.

Operating unit:

There are five keys and the plain text display on the operating
unit for parameter setting and control of the controller.

LECOM1:

LECOM1 is a protocol for control and parameter setting of the
unit via a PC or other hosts. The signals are processed to the
interface standards RS232C and RS485. The controller can be
connected to a superimposed system via X6.

LECOM2:

For very difficult requirements, the controller can be parameter-
set and operated with LECOM2 via fieldbus connection
modules for standard bus systems (InterBus-S, PROFIBUS
etc.).

Code

Name

Possible settings

Code

Name

Lenze Selection

Info

C001

¤ Operating

mode

0

Control

Parameter setting

-0-

Terminals

Keypad

-1-

Keypad

Keypad

-2-

Terminals

LECOM1

-3-

LECOM1

LECOM1

-4-

Terminals

LECOM2 (*)

-5-

LECOM2 (*) LECOM2 (*)

-6-

LECOM2 (*) Keypad

-7-

LECOM2 (*) LECOM1

With C001 =
-2-, -3-, -4-, -5-, -7-, TRIP must be reset
(C043) via the interface or the terminal.
With LECOM2, TRIP reset is also possible
via the control word of the process data
channel.

(*) Fieldbus

Note!

With control via keypad, LECOM1 and LECOM2, the terminal functions controller
enable (X1/28), quick stop (X1/21 and X1/22) and the additional setpoint (X1/6)
remain the same in the configurations C005 = -1X-, -4X-, -5X-.