Absolute value generator, Configuration – Lenze EDS4900U-REG User Manual

Page 162

Advertising
background image

Configuration

7-71

48XX/49XXSHB0399

Example

The analog inputs terminal 8 and terminal 6 are to be connected (division) via the
arithmetic block 2 and then be assigned to the code C046 ”main set-value”.

Procedure

( Select C145 = -4-, terminal 8
( Assign C146 = -14-, arithmetic block 2 input 1
( Select C145 = -3-, terminal 6
( Assign C146 = -15-, arithmetic block 2 input 2
( Select C145 = -10-, arithmetic block 2
( Assign C146 = -1-, main set-value (C046)
( C191 = -4-, division: select input 1 / input 2 (C338 / C339).
3. Functions

For all arithmetic blocks the following functions can be preselected (example for
arithmetic block 2):

with C191 = -0-, output

= C338 (C339 not processed)

with C191 = -1-, output

= C338 + C339

100%

= 50% + 50%

with C191 = -2-, output

= C338 - C339

50%

= 100% - 50%

with C191 = -3-, output

= C338

:

C339

100%

= 100%

:

100%

with C191 = -4-, output

= C338 / |C339|

1%

= 100% / 100%

with C191 = -5-, output

= C338 / (100% - C339)

200%

= 100% / (100% - 50%)

Arithmetic block 1 (fixed)

Code

Name

Possible settings

Code

Name

Lenze Selection

Info

C190*

¤ Arithmetic

block 1

1

-0-

Output = C046

-1-

Output = C046 + C049

-2-

Output = C046 - C049

-3-

Output = C046

¼ C049

-4-

Output = C046 / |C049|

-5-

Output = C046 / (100% - C049)