Configuration – Lenze EDS4900U-REG User Manual

Page 182

Advertising
background image

Configuration

7-91

48XX/49XXSHB0399

Therefore, the current limitation must be reduced depending on the
compensation of the DC machine and the actual speed.

I

max

100%

n

0

n

1

n

2

Limit value 1

Limit value 2

0

n

act

(C310)

(C311)

(C022, C023)

(C312)

(C313)

(C314)

4900Str079

FIG 7-52

Parameter assignment to the speed-dependent armature current limitation

The speed-dependent current limitation acts on the current set-value C063
(reference I

max

: C022, C023).

Linear characteristic

If the current limit is to be lowered linearly (depending on the machine used), the
speed at which the reduction is to begin is set under C313. The slope of the
characteristic is set under C311 and C314.

Non-linear characteristic

By means of a second section with linear slope, the non-linear characteristic can
be approximated with two vertex.
The speed at which the lowering of the current limit is to start can be set with the
parameter C312. The slope of the 1st section is set under codes C310 and C313.
The 2nd section is parameterised with codes C311 and C314.

Motor types

Usually, compensated machines require a current reduction as of approx. 1:3 field
weakening operation. Uncompensated machines require the reducation as of
1:1.2 field weakening operation. The current limitation is then to be lowered with
the function 1/n.

Show/Hide Bookmarks