The Resources



DMS 3.2 EN 02/2011 TD29

361

DP parameters of the DP master

This dialog shows the following parameters extracted from the device file of the DP
master (The dialog might have a different title, which is defined in the configuration
file):

DP parameters dialog for DP master

Info

Manufacturer, GSD Revision, ID (identification number), HW Release and SW
Release
(hard- and software version), GSD-Filename

Addresses

Station address: The allowable range extends from 0 to 126. Each device newly
inserted on a bus line is automatically provided the next higher address. (note:
Address 126 is the default DP slave address). Manual entry is possible; addresses are
tested for duplication.

Highest station address: The highest station address (HSA) assigned on the bus is

displayed. Here, a lower address can also be entered in order to narrow the GAP
range (that is, the address range within which the search for newly-active devices is
carried out).

Mode

Auto Clear Mode: If this option is activated, the outputs of the slaves will be
switched to a save state in error case and the master will change from state
"operate" to "clear".

Automatic Startup: If this option is not activated, the master must be started

manually. However it depends on the driver, whether the setting is evaluated.

The GSD-file pertaining to a device can be opened and examined using the GSD-file
button.