The following action types (Possible actions) are supported (for a definition of a
message text see below):

Action

Description

Settings to be done in the corresponding dialog:

Save:

The alarm event will be
saved internally, in order to

be given out e.g.in a log-
file. Please regard: In this

case the log-file must be
defined in the
configuration of the alarm

group !

The settings are done in the Alarm group definition in the
Alarm saving dialog

Print:

A message text is sent to a

printer.

Printer: Select one of the printers defined on the local system;

Outputtext: Message text (see below) which should be
printed out

Please note that this function is not supported for Target-

Visualization !

Message: In the current visualization

of the alarm a message
window will be opened
showing the defined text.

Message: Message text to be displayed in the message
window

Please note that this function is not supported for Target-
Visualization !

E-Mail:

An E-Mail containing the
defined message will be
sent.

From: E-Mail address of sender; To: E-Mail address of
recipient; Subject: any subject; Message: Message text (see
below); Server: Name of the E-Mail server

Variable:

A variable of the PLC
Designer program will get
the alarm status resp. a
message text string.

Variable: Variable name: You can select project variables via
the input assistant (<F2>): A boolean variable will indicate the
alarm states NORM =0 and INTO=1, an integer variable will
indicate the alarm states NORM =0, INTO =1, ACK =2, OUTOF
=4; a string variable will get the message text defined in field;
Message (see below)

Execute:

An executable file will be

started as soon as the
alarm event occurs.

Executable file: name of the file to be executed (e.g.

notepad.exe, you can use the "..." button to get the standard
dialog for selecting a file; Parameter: appropriate parameter(s)

which should be attached to the call of the exe-file