L-force | PLC Designer

Compiler Errors and Warnings

624

DMS 3.2 EN 02/2011 TD29



4372

"Step '<name>': Time limit needs type 'TIME'"

Define the time limits of the step in the step attributes by using a variable of type
TIME or by a time definition in correct format (e.g "t#200ms").

4373

"IEC-actions are only allowed with SFC-POUs"

There is an action assigned to a non-SFC-POU (see in the Object Organizer), which is
programmed in SFC and which contains IEC actions. Replace this action by one which
contains no IEC actions.

4374

"Step expected instead of transition '<name>'"

The SFC POU is corrupt, possibly due to any export-import actions.

4375

"Transition expected instead of step '<name>'"

The SFC POU is corrupt, possibly due to any export-import actions.

4376

"Step expected after transition '<name>'"

The SFC POU is corrupt, possibly due to any export-import actions.

4377

"Transition expected after step '<name>'"

The SFC POU is corrupt, possibly due to any export-import actions.

4400

Import / conversion of POU '<name>' contains errors resp. is not complete."

The POU cannot be converted to IEC 61131-3 completely.

4401

"S5 time constant <number> seconds is too big (max. 9990s)."

There is no valid BCD coded time in the accu.