Settings: This button opens the dialog Settings for <networktype> with the following
configuration parameters:

UDP:
Use standard If this button is pressed, Port 1202 will be defined for the data
exchange with the other network participants. The Broadcast address will be set to
"255 . 255 . 255 . 255" , which means, that the data exchange will be done with all
participants in the network.
Port for all networks: Enter here a desired port number to overwrite the standard
setting (see above, Use standard). Make sure that the other nodes in the network
define the same port! If you have more than one UDP connection defined in the
project then the port number will be automatically modified in all configuration
sets according to the input you make here.
Broadcast address: Enter here an address resp. the address range of a sub-network,
if you want to overwrite the standard setting (e.g. "197 . 200 . 100 . 255", if you
want to communicate with all nodes with IP-addresses 197 . 200 . 100 . x).
Regard for Win32 systems, that the Broadcast addresses must match the subnet
mask of the TCP/IP configuration of the PC !

Dialog 'Settings for UDP

CAN:
Controller Index: Index of the CAN Controller, by which the variables should be
transferred.