L-force | plc designer – Lenze PLC Designer PLC Designer (R2-x) User Manual

Page 367

Advertising
background image

L-force | PLC Designer

The Resources



DMS 3.2 EN 02/2011 TD29

365

DP parameters of a DP slave

This dialog shows the following parameters extracted from the device file of the DP
slave (The dialog might have a different title, which is defined in the configuration
file):

DP parameters dialog for a DP slave

Info

Manufacturer, GSD Revision, HW Release and SW Release (hard- and
software version), GSD-Filename, Slavetype

Standard parameter

Identnumber: Unique ident number assigned by the PNO for this device
type. Allows unambiguous reference between a DP slave and the

corresponding GSD-file.

TSDR (Tbit*): Time Station Delay Responder: Reaction time, the earliest
time after which the slave is permitted to respond to the master. (min. 11

TBit)

* TBit: Time unit for transfer of a bit on the PROFIBUS; Reciprocal value of

the transmission rate; e.g. 1 TBit at 12MBaud=1/12.000.000 Bit/sec=83ns

Lock/Unlock: Slave is locked or released to other masters:

0: min.TSDR and slave-specific parameters may be overwritten
1: Slave released to other masters,
2: Slave locked to other masters, all parameters are accepted;

3: Slave released to other masters

Advertising