background image

4.4 Limiting Torque

4-29

Operation

4.4 Limiting Torque

The SERVOPACK provides the following three methods for limiting output torque to protect the machine.

4.4.1 Internal Torque Limit

This function always limits maximum output torque by setting values of following parameters.

The setting unit is a percentage of the rated torque.

Note 1. Too small a torque limit setting will result in insufficient torque during acceleration and deceleration.

2. The maximum torque of the servomotor is used whenever the value exceeds the maximum torque is set.

Waveform of Torque

Limiting Method

Description

Reference

Section

Internal torque limit

Always limits torque by setting the parameter.

4.4.1

External torque limit

Limits torque by input signal from the host controller.

4.4.2

Torque limit with command

option module

Limits torque by inputting a desired torque limit command to the

command option module from the host controller.

Refer to the manual

of the command

option module to

be connected.

Pn402

Forward Torque Limit

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 800

1%

800

Immediately

Setup

Pn403

Reverse Torque Limit

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 800

1%

800

Immediately

Setup

Speed

Position

Torque

Speed

Position

Torque

Speed

Maximum torque

t

Speed

Pn403

Pn402

Limiting torque

t

No Internal Torque Limit

(Maximum Torque Can Be Output)

Internal Torque Limit