Yaskawa Sigma-5 User Manual: Design and Maintenance - Rotary Motors User Manual

Page 54

Advertising
background image

3 Wiring and Connection

3.1.2 Using a Standard Power Supply Input (Single-phase 100-V, Three-phase 200-V, or Three-phase 400-V)

3-10

(5) Molded-case Circuit Breaker and Fuse Capacities

The following table describes the molded-case circuit breaker and fuse capacities of the SERVOPACK.

Note 1. To comply with the low voltage directive, connect a fuse to the input side. Select the fuse or molded-case circuit

breaker for the input side from among models that are compliant with UL standards.
The table above also provides the net values of current capacity and inrush current. Select a fuse and a molded-
case circuit breaker which meet the breaking characteristics shown below.

• Main circuit, control circuit: No breaking at three-times the current values of the table for 5 s.
• Inrush current: No breaking at the same current values of the table for 20 ms.

2. In accordance with UL standards, the following restrictions apply.

Main Circuit

Power

Supply

Maximum

Applicable

Motor

Capacity

[kW]

SERVOPACK

Model

SGDV-

Power Supply

Capacity per

SERVOPACK

[kVA]

Current Capacity

Inrush Current

Main Circuit

[Arms]

Control

Circuit

[Arms]

Main

Circuit

[A0-p]

Control

Circuit

[A0-p]

Single-phase,

100-V

0.05 R70F

0.2

1.5

0.38

16.5

35

0.1 R90F

0.3

2.5

0.2 2R1F

0.7

5

0.4 2R8F

1.4

10

Three-phase,

200-V

0.05 R70A

0.2

1.0

0.2

33

70

0.1 R90A

0.3

1.0

0.2 1R6A

0.6

2.0

0.4 2R8A

1

3.0

0.5

3R8A

1.4

3.0

33

0.75 5R5A

1.6

6.0

1.0

7R6A

2.3

6.0

1.5

120A

3.2

7.3

0.25

2.0

180A

4

9.7

3.0

200A

5.9

15

5.0

330A

7.5

25

0.3

65.5

6.0

470A

10.7

29

7.5

550A

14.6

37

11

590A

21.7

54

0.45

109

48

15

780A

29.6

73

Three-phase,

400-V

0.5

1R9D

1.1

1.4

1.2

17

1.0

3R5D

2.3

2.9

1.5

5R4D

3.5

4.3

2.0

8R4D

4.5

5.8

1.4

34

3.0

120D

7.1

8.6

5.0

170D

11.7

14.5

57

6.0

210D

12.4

17.4

1.5

34

7.5

260D

14.4

21.7

11

280D

21.9

31.8

1.7

68

15

370D

30.6

43.4

SERVOPACK
Model SGDV-

Restrictions

180A, 200A

Available rated current for molded-case circuit breaker: 40 A or less

330A

• Available rated current for non-time delay fuse: 70 A or less
• Available rated current for time delay fuse: 40 A or less
• Do not use single wires.

Advertising