6 (2) setting monitor factor, 3) related parameters – Yaskawa Sigma-5 User Manual: Design and Maintenance - Rotary Motors User Manual

Page 143

Advertising
background image

5 Adjustments

5.1.3 Monitoring Analog Signals

5-6

(2) Setting Monitor Factor

The output voltages on analog monitor 1 and 2 are calculated by the following equations.

(3) Related Parameters

Use the following parameters to change the monitor factor and the offset.

Analog monitor 1 output voltage = (-1)

×

Analog monitor 2 output voltage = (-1)

×

(Pn006=n.00

غغ

) (Pn552)

(Pn007=n.00

غغ

×

Multiplier + Offset voltage [V]

×

Multiplier + Offset voltage [V]

(Pn550)

(Pn551)

(Pn553)

Signal selection

Signal selection

Pn550

Analog Monitor 1 Offset Voltage

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

-10000 to 10000

0.1 V

0

Immediately

Setup

Pn551

Analog Monitor 2 Offset Voltage

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

-10000 to 10000

0.1 V

0

Immediately

Setup

Pn552

Analog Monitor Magnification (

×1)

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

-10000 to 10000

0.01 times

100

Immediately

Setup

Pn553

Analog Monitor Magnification (

×1)

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

-10000 to 10000

0.01 times

100

Immediately

Setup

Speed

Position

Torque

Speed

Position

Torque

Speed

Position

Torque

Speed

Position

Torque