1 anti-resonance control adjustment function, Caution – Yaskawa Sigma-5 User Manual: Design and Maintenance - Rotary Motors User Manual

Page 177

Advertising
background image

5 Adjustments

5.6.1 Anti-resonance Control Adjustment Function

5-40

5.6 Anti-resonance Control Adjustment Function (Fn204)

This section describes how to adjust the anti-resonance control.

5.6.1 Anti-resonance Control Adjustment Function

The anti-resonance control adjustment function increases the effectiveness of the vibration suppression after

one-parameter tuning.

The anti-resonance control adjustment function (Pn204) is an effective way to control the frequent vibration

between 100 Hz and 1000 Hz when the control gain increases.

Perform one-parameter tuning (Fn203) or use another method to increase the responsiveness after performing

this function. If the vibration gain is increased with one-parameter tuning performed, vibration may result

again. If that occurs, perform this function again to fine-tune the settings.

(1) Before Performing Anti-Resonance Control Adjustment Function

Check the following settings before performing anti-resonance control adjustment function.

a) A message (NO-OP) indicating that no operations are possible will be displayed, if all of the following

conditions are not met.

• The tuning-less function must not be enabled.
• Test without motor function must not be enabled. (Pn00C.0=0)
• Torque control must not be selected.

b) Observe the following condition to ensure operation.

• The write prohibited setting (Fn010) must not be set.

CAUTION

• If this function is executed, related parameters will be set automatically. Therefore, there will be a large

response change after this function is enabled or disabled. Enable the function in a state where the

machine can come to an emergency stop at any time to ensure the safety operation of the machine.

• Be sure to set a suitable value for the moment of inertia ratio (Pn103) using advanced autotuning before

executing the anti-resonance control adjustment function. If the setting greatly differs from the actual

moment of inertia ratio, normal control of the SERVOPACK may not be possible, and vibration may result.

• This function detects vibration between 100 and 1,000 Hz. Vibration will not be

detected for frequencies outside of this range, and instead, “F----” will be displayed. If
that occurs, use one-parameter tuning with tuning mode 2 selected to automatically
set a notch filter or use the vibration suppression function (Fn205).

• Vibration can be reduced more effectively by increasing the present damping gain

(Pn163). The amplitude of vibration may become larger if the damping gain is exces-
sively high. Increase the vibration gain from about 0% to 200% in 10% increments
while checking the effect of vibration reduction. If the effect of vibration reduction is
still insufficient at a gain of 200%, cancel the setting, and lower the control gain using
a different method, such as one-parameter tuning.

Advertising