6 Utility Functions (Fn

)

6-26

6.16 Vibration Detection Level Initialization (Fn01B)

This function detects vibration when servomotor is connected to a machine and automatically adjusts the

vibration detection level (Pn312) to output more exactly the vibration alarm (A.520) and warning (A.911).

Use this function if the vibration alarm (A.520) or warning (A.911) is not output correctly when a vibration

above the factory setting vibration detection level (Pn312) is detected. In other cases, it is not necessary to use

this function.

The vibration detection function detects vibration elements according to the motor speed.

If the vibration exceeds the detection level calculated by the following formula, the alarm or warning will be
output according to the setting of vibration detection switch (Pn310).

<Remarks>
The vibration alarm or warning detection sensibility differs depending on the machine conditions. In this
case, a detection sensibility fine adjustment can be set in the detection sensibility Pn311.

(1) Operating Procedure

Follow the steps to adjust the parameter Pn312.

Parameter

Meaning

When Enabled Classification

Pn310

n.

0

Does not detect vibration. (Factory setting)

Immediately

Setup

n.

1

Outputs the warning (A.911) when vibration is

detected.

n.

2

Outputs the alarm (A.520) when vibration is detected.

• The vibration may not be detected because of improper servo gains. Also, not all

kinds of vibrations can be detected. Use the detection result as a guideline.

• Set a proper moment of inertia ratio (Pn103). Improper setting may result in the vibra-

tion alarm, warning misdetection, or non-detection.

• The references that are used to operate your system must be input to execute this

function.

• Execute this function under the operation condition for which the vibration detection

level should be set.

• Execute this function to set the vibration detection level while the motor speed

reaches at least 10% of its maximum.

Detection level =ޓVibration detection level (Pn312[min

-1

])× Detection sensibility (Pn311[%])

100

Step

Display Example

Keys

Description

1

Press the

Key to open the Utility Function Mode

main menu and select Fn01B.

2

Press the

Key. The display is switched to the

execution display of Fn01B.
Note: If the display is not switched and “NO-OP” is

displayed in the status display, the Write Prohib-
ited Setting (Fn010 = 0001) is set. Check the
setting and reset. (Refer to 6.12.)

R U N

− F U N C T I O N −

F n 0 1 4 : O p t I n i t
F n 0 1 B : V i b l − v l I n i t

F n 0 1 E : S v M o t O p I D
F n 0 1 F : F B O p M o t I D

L e v e l I n i t

R U N

V i b r a t i o n D e t e c t

S t a r t : [ D A T A ]

R e t u r n : [ S E T ]