5.6 Anti-resonance Control Adjustment Function (Fn204)

5-41

Adjustments

5.6.2 Anti-resonance Control Adjustment Function Operating Procedure

With this function, a control reference is sent, and the function is executed while vibration is occurring.

Anti-resonance control adjustment function is performed from the Digital Operator (option) or SigmaWin+.

The following three methods can be used for the anti-resonance control adjustment function. Select and use

the best method.

1. With Undetermined Vibration Frequency Before Adjusting the Anti-resonance Control
2. With Determined Vibration Frequency Before Adjusting the Anti-resonance Control
3. For Fine-tuning After Adjusting the Anti-resonance Control

The operating procedures from the Digital Operator are described here.

Refer to the

Σ

-V series User’s Manual, Operation of Digital Operator (SIEP S800000 55) for basic key oper-

ations of the Digital Operator.

(1) With Undetermined Vibration Frequency Before Adjusting the Anti-resonance

Control

Step

Display after Operation

Keys

Operation

1

Press the

Key to view the main menu for the

utility function mode.
Use the

or

Key to move through the list,

select Fn204.

2

Press the

Key to display the initial setting screen

for tuning mode.
Note: If the display does not switch and “NO-OP” is

displayed, take corrective action after checking

the items given in 5.6.1 (1) Before Performing
Anti-resonance Control Adjustment Function.

3

Press the

or

Key and select the tuning mode

“0”.

4

Press the

Key while “Tuning Mode = 0" is dis-

played. The screen shown on the left will appear. The

detection of vibration frequencies will start and
“freq” will blink. Return to step 3 if vibration is not
detected.
Note: If a vibration is not detected even though a

vibration has occurred, lower the vibration
detection sensibility (Pn311). When this
parameter is lowered, the detection sensitivity
will be increased. Vibration may not be
detected accurately if too small value is set.

5

The vibration frequency will be displayed if vibration
is detected.

Waveform

㧾㨁㧺ޓ   ̆㧲㨁㧺㧯㨀㧵㧻㧺̆
㧲㨚㧞㧜㧟㧦㧻㨚㨑㧼㨞㨙㨀㨡㨚
㧲㨚㧞㧜㧠㧦㧭㨂㨕㨎ޓ㧿㨡㨜
㧲㨚㧞㧜㧡㧦㨂㨕㨎ޓ㧿㨡㨜
㧲㨚㧞㧜㧢㧦㧱㨍㨟㨥ޓ㧲㧲㨀

㧾㨁㧺    ̆ 㨂㨕㨎 㧿㨡㨜̆

㨀㨡㨚㨕㨚㨓 㧹㨛㨐㨑 㧩 㧜

Status Display

㧾㨁㧺    ̆ 㨂㨕㨎 㧿㨡㨜̆

㨀㨡㨚㨕㨚㨓 㧹㨛㨐㨑 㧩 㧜

㧾㨁㧺    ̆ 㨂㨕㨎 㧿㨡㨜̆

 㨒㨞㨑㨝 㧩 㧙㧙㧙㧙 㧴㨦
 㨐㨍㨙㨜 㧩 㧜㧜㧜㧜

㧾㨁㧺    ̆ 㨂㨕㨎 㧿㨡㨜̆

 㨒㨞㨑㨝 㧩 㧜㧠㧜㧜 㧴㨦
 㨐㨍㨙㨜 㧩 㧜㧜㧜㧜

Error

Error

Error

Torque reference

Positioning completed

Positioning completed

signal

signal

Torque reference

Positioning completed

signal

Advertising