4.5 Absolute Encoders

4-35

Operation

4.5.2 Absolute Data Request (Sensor ON Command)

The Sensor ON command must be sent to obtain absolute data as an output from the SERVOPACK.

The Sensor ON command is sent at the following timing.

Note: Command sending method differs in accordance with the connected command option module.

For details, refer to the manual for the command option module that is connected.

∗ Turn OFF the Sensor ON command to turn OFF the control power supply.

SERVOPACK control
power supply

5 seconds max.

ON

OFF

OFF

ON (Normal status)

OFF

ON

50 ms

Rotational serial data

(Phase A)

(Phase B)

(Phase B)

Approx.
15 ms

400 ms max.

1 to 3 ms

60 ms max.
(90 ms typ.)

The servomotor will not be turned ON even if the Sensor ON command is received during this interv

ALM signal OFF
(Alarm status)

Sensor ON command

PAO

PBO

Servomotor power

Undefined

Undefined

(Phase A)

OFF

OFF

OFF

OFF

*

ON

Incremental
pulses

Incremental
pulses

Initial incremental
pulses

Initial incremental
pulses

46