Wiring of the standard device

Standard devices in the power range 0.37 ... 11 kW
Mains connection, DC supply

5

5.4
5.4.3

l

5.4−4

EDSVF9333V EN 6.2−04/2012

5.4.3

Mains connection, DC supply

)

Note!

ƒ

If a mains filter or RFI filter is used and the cable length
between mains/RFI filter and drive controller exceeds
300 mm, install a shielded cable.

ƒ

For DC−bus operation or DC supply, we recommend using
shielded DC cables.

(

Stop!

ƒ

To avoid damaging the PE stud, always install the shield sheet
and the PE connection in the order displayed. The required
parts are included in the accessory kit.

ƒ

Do not use lugs as strain relief.

M6

M5

2 3

4 5

6 7

1

0

L1 L2 L3 +UG -UG

PE

a

1.7 Nm
15 lb-in

PE

M5
3.4 Nm
30 lb-in

a

}

+

PE

4
2

8

0

7

9300vec130

Fig. 5.4−2

Installation of shield sheet for drive controllers 0.37 ... 11 kW

0 PE stud

1 Screw on M5 nut and tighten hand−tight

2 Slide on fixing bracket for shield sheet

3 Slide on serrated lock washer

4 Slide on PE cable with ring cable lug

5 Slide on washer

6 Slide on spring washer

7 Screw on M5 nut and tighten it

8 Screw shield sheet on fixing bracket with two M4 screws (a)

Shield sheet installation