Wiring of the standard device, Danger – Lenze EVF9333−xV User Manual

Page 82

Advertising
background image

Wiring of the standard device

Important notes
Protection of persons

5

5.1
5.1.1

l

5.1−2

EDSVF9333V EN 6.2−04/2012

The terminals X1 and X5 have a double (reinforced) insulation in accordance
with EN 61800−5−1. The protection against accidental contact is ensured
without any further measures.

{

Danger!

ƒ

Terminals X3, X4, X6, X8, X9, X10, X11 have a single basic
insulation (single isolating distance).

ƒ

Protection against accidental contact in case of a defective
isolating distance is only guaranteed through external
measures, e.g. double insulation.

ƒ

If an external DC 24 V voltage source is used, the insulation
level of the controller depends on the insulation level of the
voltage source.

59 39 A1 A2 A3 A4 E1 E2 E3 E4 E5

ST1 ST2

28

L1

24 VDC

N

X1

X5

X3 X4 X6 X8 X9 X10 X11

W

V

U

PE

PE

L1

L2

L3

+U

G

-U

G

9300VEC050

Fig. 5.1−1

Electrical isolation between power terminals, control terminals and housing

Double (reinforced) insulation
Basic insulation

Only replace defective fuses in the deenergised state to the type specified.

Only carry out the safety−related disconnection of the controller from the
mains via a contactor on the input side or a manually operated toggle switch.

Electrical isolation

Replacing defective fuses

Disconnecting the controller
from the mains

Advertising
This manual is related to the following products: