2 resetting system error messages, Resetting system error messages, Troubleshooting and fault elimination – Lenze EVF9333−xV User Manual

Page 459

Advertising
background image

Troubleshooting and fault elimination

System error messages

Resetting system error messages

9

9.5

9.5.2

l

9.5−5

EDSVF9333V EN 6.2−04/2012

Remedy

Cause

Description

Fault message

Remedy

Cause

Description

Display

No.

0140

ID1

Error during motor data
identification.

No motor connected.

Check motor connection.

Stator resistance too high.

Check entered motor data.

Controller inhibited externally.

Enable controller and repeat
motor data identification. The
controller enable must be
pending continuously until the
end of the identification process.

0141

ID2

Error during motor data
identification.

Motor too small.

l

Check entered motor data. For
parameterisation with Global
Drive Control, use the input
assistant for motor data.

l

The measurements for the
inverter error characteristic
and the stator resistance are
correct (save measured values
in C0003). For the operating
mode V/f characteristic control
the motor data identification
can be completed.

Controller inhibited externally.

Enable controller and repeat
motor data identification. The
controller enable must be
pending continuously until the
end of the identification process.

x200

NMAX

Maximum system speed (C0596)
has been exceeded.

l

Active load (e.g. for hoists) is
too high.

l

Drive is not speed−controlled,
torque is excessively limited.

l

Check drive dimensioning.

l

Increase torque limit, if
necessary.

l

Switch off monitoring
(C0607 = 3).

Representation of the error number:
x

0 = TRIP, 1 = message, 2 = warning
E. g. "2091": An external monitoring function has triggered EEr warning

9.5.2

Resetting system error messages

Response

Measures for resetting the fault message

TRIP

Note!
If a TRIP source is still active, the pending TRIP cannot be reset.

Resetting the TRIP can be effected by:

l

Pressing the keypad XT EMZ9371 BC

ð S. Then press U to re−enable the controller.

l

Setting code C0043 = 0.

l

Control word C0135, bit 11

l

Control word AIF

l

Control word of system bus (CAN)

After resetting the TRIP, the drive remains at standstill.

Message

Danger!
After elimination of the fault, the fault message is cancelled automatically and the drive restarts
automatically.

Warning

After elimination of the fault, the fault message is cancelled automatically.