3 maximum speed, 4 motor, Maximum speed – Lenze EVF9333−xV User Manual

Page 341: Motor, Configuration

Advertising
background image

Configuration

Monitoring

Maximum speed

8

8.3

8.3.3

l

8.3−3

EDSVF9333V EN 6.2−04/2012

8.3.3

Maximum speed

(

Stop!

Destruction of the drive!

ƒ

If the fault is triggered, the drive is without torque.

ƒ

In the event of an actual speed value encoder failure it is not
guaranteed that the monitoring responds.

Protective measures:

ƒ

Use a mechanical brake if necessary.

ƒ

Special, system−specific measures are to be taken.

The NMAX fault is triggered if the system speed (MCTRL−NACT)

ƒ exceeds the value set under C0596 or

ƒ exceeds the maximum speed n

max

(C0011) by twice the max. speed

value.

A fault initiates TRIP NMAX. Other responses cannot be set.

8.3.4

Motor

Fault OC1 is triggered if the motor current exceeds the 2.25−fold rated
controller current.

If a fault occurs, TRIP OC1 is triggered. Other responses cannot be set.

Fault OC2 is activated in the case of a

ƒ Short circuit to frame of the motor,

ƒ Short circuit of a phase to the shield,

ƒ Short circuit of a phase to PE,

ƒ Too high capacitive charging current of the motor cable.

The response can be defined in C0574.

Fault OC3 is activated in the case of a too great load during acceleration. The
acceleration times or deceleration times (C0012, C0013, C0105) are set too
short in proportion to the load.

If a fault occurs, TRIP OC3 is activated. Other responses cannot be set.

Overcurrent in the motor
cable (OC1)

Earth fault in the motor cable
(OC2)

Overload during acceleration
or deceleration (OC3)