Troubleshooting and fault elimination

Troubleshooting

Status display via controller LEDs

9

9.2

9.2.1

l

9.2−1

EDSVF9333V EN 6.2−04/2012

9.2

Troubleshooting

A breakdown can be detected quickly via the LEDs at the controller or via the
status information at the keypad.

Analyse the error using the history buffer. The list of fault messages gives
you advice how to remove the fault. (

9.5−1)

9.2.1

Status display via controller LEDs

During operation the operating status of the controller is shown by 2 LEDs.

LED

Operating status

Red



Green

‚

Off

On

Controller is enabled

On

On

Mains is switched on and automatic
start is inhibited

Off

Blinking
slowly

Controller is inhibited

Off

On

Motor data identification is being
performed

Blinking
quickly

Off

Undervoltage

Blinking
slowly

Off

Active fault

9.2.2

Fault analysis with the history buffer

Faults can be retraced via the history buffer. Fault messages are stored in the
8 memory locations in the order of their appearance.

The memory locations can be retrieved via codes.

Detecting breakdowns

Analysing errors