Troubleshooting and fault elimination

Fault elimination

Behaviour in case of overvoltage in the DC bus (OU message)

9

9.4

9.4.3

l

9.4−3

EDSVF9333V EN 6.2−04/2012

9.4.3

Behaviour in case of overvoltage in the DC bus (OU message)

If the DC−bus voltage (U

DC

) exceeds the switch−off threshold OU, the pulse

inhibit is set. At the same time, an internal timing element starts for a delay
time (C0912).

The pulse inhibit is deactivated if the voltage falls below the switch−on
threshold OU and the delay time has elapsed.

Switching thresholds in case of overvoltage in the DC bus (OU):

Mains voltage range

C0173

Switch−off threshold

OU

Switch−on threshold

OU

< 400 V

Operation with /
without brake
chopper

0

770 V

755 V

400 V

Operation with /
without brake
chopper

1

*

770 V

755 V

460 V

Operation with /
without brake
chopper

2

770 V

755 V

480 V

Operation without
brake chopper

3

770 V

755 V

480 V

Operation with brake
chopper

4

800 V

785 V

*

Lenze setting

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0912 OV delay time

à

{1 ms}

− Delay time of the pulse enable

after an OU message

à

Depending on C0082, C0086,
C0087, C0088, C0089, C0090,
C0091, C0092
A change of one of the codes
resets C0912 to the time of the
selected motor

l

The time is derived from the
double rotor time constant

^
8.2−25

^
8.2−48

^
9.4−3

Description