Configuration, Code table – Lenze EVF9333−xV User Manual

Page 363

Advertising
background image

Configuration

Code table

8

8.5

l

8.5−15

EDSVF9333V EN 4.0−11/2007

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0143 limit 2 kHz

0.0

0.0

{0.1 Hz}

20.0 Speed−dependent switching

threshold

l

Threshold for automatic
switching frequency reduction

l

The controller changes
automatically to 2 kHz when
this value falls below the
threshold

^
8.2−25

^
8.2−48

C0144

s

OH switch

1

0

Switch off

Switch−over is not
active

Temperature−dependent
switching frequency reduction

l

If the heatsink temperature set
in C0122 is reached (warning

OH4), the controller switches
to 2 kHz

1

Switch on

Switch−over is
active

C0145

s

select ref

1

Selection of the flying restart
mode

l

Reference speed with which
the flying restart process is
started

^
8.2−36

^
8.2−65

0

REF: C0011

Maximum speed

1

REF: N−ACT

Last current speed

2

REF: N−SET

Defined main speed setpoint
It is referenced to the setpoint
signal at input NSET−N of the
function block NSET.
If the setpoint signal at input
NSET−N is missing, it is referenced
to the active JOG setpoint
(C0039/x)

C0146

fly current

0

−500

{1}

500 Flying restart circuit, quantity of

current during search process

l

Influences the current injection
during search process

l

±500

» ±39 % of I

max

l

The initial value amounts to

» 8 % of I

max

^
8.2−36

^
8.2−65

C0147 fly dt−f

0

−82

{1}

82 Flying restart circuit, search speed

during flying restart process

l

For drives with great
centrifugal masses, reduce the
search speed, if required

l

±82

¢ ±5.0 Hz

C0148

s

ident run

0

0

WRK
stop

Ready

Motor data identification
1. Inhibit controller, wait until

drive has stopped

2. Enter the correct values of the

motor nameplate into C0087,
C0088, C0089, C0090, C0091

3. Set C0148 = 1, confirm with

v

4. Enable controller

The identification
– starts,

c goes off. The

motor "whistles" but does
not rotate!

– lasts approx. 1 ... 2 min
– is completed when

c is lit

again

5. Inhibit controller:

^
6.6−14

1

WRK run Start identification

Advertising
This manual is related to the following products: