Wiring of the standard device

Basics for wiring according to EMC
Motor cable

5

5.3
5.3.3

l

5.3−2

EDSVF9333V EN 6.2−04/2012

– it is not interrupted.

ƒ If the motor cable must be opened all the same (e.g. due to chokes,

contactors, or terminals):
– The unshielded cable ends may not be longer than 100 mm

(depending on the cable cross−section).

– Install chokes, contactors, terminals etc. spatially separated from

other components (with a min. distance of 100 mm).

– Install the shield of the motor cable directly before and behind the

point of separation to the mounting plate with a large surface.

ƒ Connect the shield with a large surface to PE in the terminal box of the

motor at the motor housing.
– Metal EMC cable glands at the motor terminal box ensure a large

surface connection of the shield with the motor housing.

Motor supply cable

Cable gland

Motor supply cable

max. 500mm

Large-surface
contact of
cable shield

Braid

Heat-shrinkable tube

Cable gland acc. to EMC with
high degree of protection

Cable gland

8200EMV023

8200EMV024

Fig. 5.3−1

Shielding of the motor cable