Commissioning – Lenze EVF9333−xV User Manual

Page 178

Advertising
background image

Commissioning

Parameter setting with the XT EMZ9371BC keypad
Commissioning example in vector control mode

6

6.3
6.3.2

l

6.3−6

EDSVF9333V EN 6.2−04/2012

Note

Switch−on sequence

l

Rated motor current (C0088)
– Lenze setting: device−dependent

Enter value for the selected motor
connection method (star/delta)!

l

Rated motor frequency (C0089)
– Lenze setting: device−dependent

l

Rated motor voltage (C0090)
– Lenze setting: device−dependent

Enter value for the selected motor
connection method (star/delta)!

l

Motor cos

j (C0091)

– Lenze setting: device−dependent

11.

For protecting the motor, set the current limit
values "I

max

current" (C0022, C0023)

Guide value

£ 2−fold rated motor current

Power range 0.37 ... 90 kW:
For dissipating the regenerative energy,
use a brake chopper or feedback
module, if necessary
Power range 110 ... 400 kW:
For dissipating regenerative energy, use
a brake resistor, if necessary
(see chapter "Commissioning"

®

"Motor adjustment"

® "Current limit

values")

A

In motor mode and generator mode (C0022)

B

Additional limitation in generator mode (C0023)
Condition: C0023 < C0022

12.

If the motor temperature is monitored with a
thermal sensor KTY:
Activate the temperature feedback with C0594
(fault SD6)
Lenze setting: 3 (switched off)

A temperature feedback with KTY has a
positive effect on the vector control,
since the motor data identification
considers the temperature influence in
the motor model.
(see chapter "Commissioning"

®

"Motor adjustment")

13.

Start the motor data identification "ident run"
(C0148)

(see chapter "Commissioning"

®"Adjusting the motor")

A

Ensure that the controller inhibit is active

misc008

59

28

X5

}

Terminal X5/28 = LOW

B

Switch on the mains

C

Set C0148 = 1

D

Enable controller

misc009

59

28

X5

}

Terminal X5/28 = HIGH
The identification starts:

l

The segment

c goes off

l

"WRK run" is displayed

l

The motor is energised and
"whistles"

l

The motor does not rotate

E

If after approx. 1 ... 2 min the segment

c is active

again, inhibit the controller

misc008

59

28

X5

}

Terminal X5/28 = LOW
The identification is completed. The
following values have been detected
and entered into the codes:

l

Inverter error characteristic
(C1753/xx)

l

Rotor resistance "Mot Rr" (C0082)

l

Stator resistance "Mot Rs" (C0084)

l

Leakage inductance "Mot Lss"
(C0085)

l

Stator inductance "Mot Ls" (C0092)

14.

Set the operating mode "vector ctrl" (C0006)
Lenze setting: 5 (V/f characteristic control)

(see chapter "Commissioning"

®

"Operating mode"

® "Vector control")

15.

Set the switching frequency "fchop" (C0018)
Lenze setting:
Power range 0.37 ... 90 kW: 6 (8/2 kHz sin)
Power range 110 ... 400 kW: 6 (4/2 kHz sin)

See chapter "Commissioning"

®

"Switching frequency of the inverter"

16.

Set your type of the speed feedback system
"Feedback type" (C0025)
Lenze setting: 1 (no feedback)

See chapter "Commissioning"

®

"Setting of speed feedback"

A

When using a TTL encoder:
Select the encoder used under C0025

Advertising