Configuration – Lenze EVF9333−xV User Manual

Page 311

Advertising
background image

Configuration

Function blocks

Internal motor control with vector control (MCTRL2)

8

8.2

8.2.7

l

8.2−49

EDSVF9333V EN 6.2−04/2012

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0006

s

Op mode

5

Selection of the operating mode
for the motor control

1

vector ctrl

Vector control
without or with
speed feedback

In case of the first selection enter
the motor data and identify them
with C0148.

^ 6.8−8

5

V / f

V/f characteristic
control

Commissioning without
identification of the motor data is
possible

l

Advantage of identification
with C0148: Improved smooth
running at low speeds

^ 6.8−4

C0010 N

min

0

0

{1 rpm}

36000

l

Reference value
for the absolute
and relative
setpoint selection
for the
acceleration and
deceleration
times

l

C0059 must be
set correctly

l

Set C0010 <
C0011

l

C0010 is only
effective in case
of analog setpoint
selection via AIN1

Important: For
parameter setting
via interface, major
changes in one step
should only be made
when the controller
is inhibited.

Minimum
speed

^
6.10−1

C0011 N

max

3000 0

{1 rpm}

36000

Maximum
speed

C0018 fchop

6

Switching frequency of the
inverter

l

General rule: the lower the
switching frequency the
– lower the power loss
– higher the noise generation
– better the concentricity

factor

– Observe derating

information at high
switching frequencies

l

The max. output frequency
(f

out

) amounts to:

– f

chop

= 16 kHz

Þf

out

= 600 Hz

– f

chop

= 8 kHz

Þf

out

= 300 Hz

– f

chop

= 4 kHz

Þf

out

= 150 Hz

– f

chop

= 2 kHz

Þf

out

= 150 Hz

^ 6.9−1

0

auto chop

automatic
change−over of the
switching
frequency
between
16/8/2 kHz

1

2 kHz sin

optimised smooth
running

2

4 kHz f_top

power−optimised

3

8 kHz f_top

power−optimised

4

8 kHz sin

noise optimised

5

16 kHz sin

noise optimised

6

auto 8/2 kHz

noise /
power−optimised
with automatic
change−over to
low switching
frequency

C0019 Thresh nact=0

0

−36000

{1 rpm}

36000 Operating threshold − automatic

DC injection brake (Auto−GSB)

l

Falling below the threshold in
C0019 activates automatic DC
injection braking when the
holding time set under C0107 >
0

^
8.2−25

^
8.2−48