5 mains choke/mains filter assignment, Mains choke/mains filter assignment, Wiring of the standard device – Lenze EVF9333−xV User Manual

Page 144

Advertising
background image

Wiring of the standard device

Standard devices in the power range 75 ... 90 kW
Mains choke/mains filter assignment

5

5.7
5.7.5

l

5.7−6

EDSVF9333V EN 6.2−04/2012

Supply conditions

Range

Description

Fuses

l

Only according to UL 248

l

Mains short−circuit current up to 10000 A

rms

: All classes permissible

l

Mains short−circuit current up to 50000 A

rms

: Only classes "J", "T" or "R"

permissible

Cables

l

Only in accordance with UL

l

The cable cross−sections specified in the following apply under the following
conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C

Observe all national and regional regulations!

9300

Rated fuse current

Cable cross−section

Fuse

L1, L2, L3, PE

Type

[A]

[AWG]

Operation with mains choke/mains filter

EVF9332−xV

175

2/0

EVF9333−xV

200

3/0

5.7.5

Mains choke/mains filter assignment

Operation with rated power (normal operation)

9300

Mains choke

Interference voltage category according to EN 61800−3 and motor cable length

Component

Component

Type

C2

max. [m]

C1

max. [m]

EVF9332−xV

ELN3−0022H130

EZN3A0022H150

25

E82ZN75334B230

10

E82ZN75334B230

50

EZN3B0022H150

50

EVF9333−xV

ELN3−0017H170

EZN3A0017H200

25

E82ZN90334B230

10

E82ZN90334B230

50

EZN3B0017H200

50

Operation with increased rated power

9300

Mains choke

Interference voltage category according to EN 61800−3 and motor cable length

Component

Component

Type

C2

max. [m]

C1

max. [m]

EVF9332−xV

ELN3−0017H170

EZN3A0017H200

25

E82ZN90334B230

10

E82ZN90334B230

50

EZN3B0017H200

50

EVF9333−xV

ELN3−0014H200

EZN3A0015H230

25

EZN3B0015H230

50

EZN3A0017H200

25

EZN3B0017H200

50

Installation to UL

Operation at rated power

Advertising