Configuration, Code table – Lenze EVF9333−xV User Manual

Page 353

Advertising
background image

Configuration

Code table

8

8.5

l

8.5−5

EDSVF9333V EN 4.0−11/2007

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0026

−199.99

{0.01 %}

199.99 Free control code FCODE 26/1 and

FCODE26/2

^ 6.5−4

See System
Manual
(extension)

1 FCODE (offset)

0.00

Offset of AIN1 (X6/1, X6/2)

2 FCODE (offset)

0.00

Offset of AIN2 (X6/3, X6/4)

C0027

−199.99

{0.01 %}

199.99 Free control code FCODE 27/1 and

FCODE27/2

1 FCODE (gain)

100.0

0

Gain AIN1 (X6/1, X6/2)

l

100 % = gain 1

2 FCODE (gain)

100.0

0

Gain AIN2 (X6/3, X6/4)

l

100 % = gain 1

C0030 DFOUT const

3

0

256 inc/rev

Function block DFOUT

l

Setting of the constant
(increments per revolution) for
the master frequency output
X10

^ 8.2−8

1

512 inc/rev

2

1024 inc/rev

3

2048 inc/rev

4

4096 inc/rev

5

8192 inc/rev

6

16384 inc/rev

C0032 FCODE

Gearbox

1

−32767

{1}

32767 Gearbox factor − numerator of the

function block DFSET

l

Freely configurable code

^
8.2−18

C0033 Gearbox

denom

1

1

{1}

32767 Gearbox factor − denominator of

the function block DFSET

^
8.2−18

C0034 Mst current

0

0

−10 V ... +10 V

Voltage / current range for analog
signals at input X6/1, X6/2

l

Observe jumper position of X3

^ 5.8−8

^ 6.5−4

1

4 mA ... 20 mA

2

−20 mA ... +20 mA

C0036 DC brk value

0.0

0.0

{0.1 A}

− Set DC braking current

à

depends on the controller

^
8.2−25

^
8.2−48

C0037 Set−value rpm

0

−36000

{1 rpm}

36000 Setpoint selection

C0038

0

{1 rpm}

36000 Suppress speed ranges, function

block NLIM1

l

Speed ranges are only run
through dynamically

l

Static behaviour in the
inhibited range is suppressed

See System
Manual
(extension)

1 N 1 start

0

Suppress speed range 1

2 N 1 stop

0

3 N 2 start

0

Suppress speed range 2

4 N 2 stop

0

5 N 3 start

0

Suppress speed range 3

6 N 3 stop

0