Configuration

Function blocks
Internal motor control with vector control (MCTRL2)

8

8.2
8.2.7

l

8.2−66

EDSVF9333V EN 6.2−04/2012

Setting

Selection

Code

Description

Search direction during
flying restart process

C0140 = 0

Lenze setting
Only search in the direction of the applied setpoint

C0140 = 1

Only search against the direction of the applied
setpoint

C0140 = 2

Only search in positive direction of rotation

C0140 = 3

Only search in negative direction of rotation

C0140 = 4

Search at first in the direction of the applied setpoint
and then against the direction

C0140 = 5

Search at first against the direction and then in the
direction of the applied setpoint

C0140 = 6

Search at first in positive then in negative direction
of rotation

C0140 = 7

Search at first in negative then in positive direction
of rotation

Reference speed for
starting the search
process

C0145 = 0

Flying restart circuit referenced to the maximum
speed (C0011).
Recommended when the motor speed is unknown

C0145 = 1

Lenze setting
Flying restart circuit referenced to the last current
motor speed

C0145 = 2

Speed setpoint, recommended when motor speed is
known

Value of current during
search process

C0146

Influences the value of current during the search
process. Reduce the value in case of motors with low
centrifugal mass (speed already increases during
search process ).

Search speed

C0147

Influences the search speed. A search process takes
approx. 1 ... 2 s. It may be required to reduce the
search speed to achieve a successful search process
(reduce value).

Activation

Selection

Code

Description

Start protection

C0142 = 0

The flying restart circuit is inactive. protection
against unexpected start−up means that a restart
requires signal change for enabling the controller (e.
g. LOW−HIGH edge at X5/28).

Automatic start

C0142 = 1

Lenze setting
Automatic start, flying restart circuit is inactive

Start after deactivating
the switch−on inhibit

C0142 = 2

Flying restart circuit is started after resetting

c

(mains connection, cancel of messages, (t > 0.5 s) or
TRIP RESET) and renewed controller enable (e. g.
LOW−HIGH edge at X5/28)

Starting without
protection against
unexpected start−up

C0142 = 3

Flying restart circuit gets active immediately. No
renewed controller enable required (e. g. LOW−HIGH
edge at X5/28).

Advertising