Dc−bus operation – Lenze EVF9333−xV User Manual

Page 468

Advertising
background image

DC−bus operation

Fuses and cable cross−sections

10

10.3

l

10.3−2

EDSVF9333V EN 6.2−04/2012

Inverter

DC fuse 14 × 51

(EFSGR0xx0AYHx)

DC fuse 22 × 58

(EFSGR0xx0AYIx)

Installation in

accordance with

EN 60204−1

Type

Mains

Rated current of fuse

Rated current of fuse

+U

G

, −U

G

Laying system

B2

C

[A]

[A]

[mm

2

]

[mm

2

]

EVF9321−xV

3/PE

400 V

12

12

1.5

1.5

EVF9322−xV

12

12

1.5

1.5

EVF9323−xV

12

12

1.5

1.5

EVF9324−xV

20

20

1.5

1.5

EVF9325−xV

40

40

4

4

EVF9326−xV

50

50

6

1)

4

1)

Pin−end connector required, since a maximum cable cross−section of 4 mm

2

can be connected to

the inverter.

Inverter

DC fuse NH1

(EFSGRxxx0ANVx)

DC fuse 22 × 58

(EFSGR0xx0AYIx)

Installation in

accordance with

EN 60204−1

Type

Mains

Rated current of fuse

Rated current of fuse

+U

G

, −U

G

Laying system

B2

C

[A]

[A]

[mm

2

]

[mm

2

]

EVF9327−xV

3/PE

400 V

100

100

25

EVF9328−xV

100

100

25

EVF9329−xV

200

25

EVF9330−xV

200

50

Inverter

DC fuse NH2

(EFSGRxxx0ANWx)

DC fuse 22 × 58

(EFSGR0xx0AYIx)

Installation in

accordance with

EN 60204−1

Type

Mains

Rated fuse current

Rated fuse current

+U

G

, −U

G

Laying system

F

C

[A]

[A]

[mm

2

]

[mm

2

]

EVF9331−xV

3/PE

400 V

250

95

EVF9332−xV

350

95

EVF9333−xV

350

95

Advertising
This manual is related to the following products: