Configuration, Overview of monitoring functions – Lenze EVF9333−xV User Manual

Page 348

Advertising
background image

Configuration

Overview of monitoring functions

8

8.4

l

8.42

EDSVF9333V

EN 6.2−04/2012

Possible responses

l Lenze setting

ü Setting possible

Monitoring

Off

Warning

Message

TRIP

CoDe

Source

Description

Error message

0015

OC5

I x t overload

MCTRL

l

0016

OC6

I

2

x t overload

MCTRL

l

0018

OC8

I

2

x t overload advance warning

MCTRL

C0606

ü

l

ü

x032

LP1

Motor phase failure
(current limit can be set in C0599)
Please note: Can only be used for asynchronous motors. The function block
MLP1 has to be entered in C0465.

MCTRL

C0597

ь

ь

l

x083

Sd3

Interruption of the digital frequency coupling. The input signal ˜Lamp
Control˜ at X9/8 is LOW
Please note: In the case of "Warning" (C0587 = 2), the drive can be
destroyed if the fault is not eliminated in time!

MCTRL

C0587

l

ь

ь

x085

Sd5

At analog input X6/1, X6/2, the input current is < 2 mA
Monitoring only possible if C0034 = 1

MCTRL

C0598

ь

ь

l

0140

ID1

Motor data identifcation − characteristic

MCTRL

l

0141

ID2

Motor data identification − motor data

MCTRL

l

Speed

0200

NMAX

Maximum speed (C0596) has been exceeded.

MCTRL

l

Time−out / overflow

0105

H05

Intern fault (memory)

Internal

l

Parameter setting

0072

PR1

Checksum error in parameter set 1

Internal

l

0073

PR2

Checksum error in parameter set 2

Internal

l

0074

PEr

Program error

Internal

l

0075

PR0

Error in the parameter sets

Internal

l

0077

PR3

Checksum error in parameter set 3

Internal

l

0078

PR4

Checksum error in parameter set 4

Internal

l

0079

PI

Fault during the parameter initialisation

Internal

l

Representation of the error number:
x

0 = TRIP, 1 = message, 2 = warning
E. g. "2091": An external monitoring has triggered EEr warning

1)

Setting only permitted by Lenze service

Advertising
This manual is related to the following products: