Lenze EVF9333−xV User Manual

Page 331

Advertising
background image

Configuration

Function blocks

Internal motor control with vector control (MCTRL2)

8

8.2

8.2.7

l

8.2−69

EDSVF9333V EN 6.2−04/2012

After a signal, the motor is decelerated to standstill when an internal ramp
function generator has been activated.

Mode of operation

ƒ Quick stop is active

– MCTRL−QSP = HIGH
– The control word DCTRL−QSP is applied
– DC injection braking (GSB) is not active (GSB has priority over quick

stop)

ƒ When quick stop is active:

– the motor decelerates to standstill with the deceleration time set in

C0105,

– A torque control is deactivated and the motor is controlled by the

speed controller.

– The torque limitations MCTRL−LO−M−LIM and MCTRL−HI−M−LIM are

deactivated.

– MCTRL−QSP−OUT is set to HIGH.

)

Note!

When the motor is at standstill, the field current is injected into
the motor.

Quick stop (QSP)

Advertising
This manual is related to the following products: