Commissioning
Changing the assignment of the control terminals X5 and X6
Free configuration of analog input signals
6.5
6.5.3
l
6.5−5
EDSVF9333V EN 6.2−04/2012
Gain and offset
Set gain (C0027) and offset (C0026) to adapt the input signal to the
application.
Input range of X6/1, X6/2
Input range
C0034
Position of jumper at X3
−10 V ... +10 V
C0034 = 0
6
4
2
5
3
1
+4 mA ... +20 mA
C0034 = 1
6
4
2
5
3
1
−20 mA ... +20 mA
C0034 = 2
)
Note!
Different settings in C0034 and of X3 result in a wrong input
signal.
Adjustment