Commissioning

Parameter setting with the XT EMZ9371BC keypad

Commissioning example in V/f characteristic control mode

6

6.3

6.3.1

l

6.3−3

EDSVF9333V EN 6.2−04/2012

Note

Switch−on sequence

18.

Set your type of the speed feedback system
"Feedback type" (C0025)
Lenze setting: 1 (no feedback)

See chapter "Commissioning"

®

"Setting of speed feedback"

A

When using a TTL encoder:
Select the encoder used under C0025

B

When using a TTL encoder with a number of
increments which cannot be set under C0025:
Set C0025 = 100
Enter the number of increments under C0420

C

If required, compensate a voltage drop in the
incremental encoder cable. Use C0421 to adjust the
supply voltage for the TTL encoder.

D

When using a HTL encoder:
Set C0025 = 101
Enter the number of increments under C0420

19.

Set the maximum speed (C0011)
Lenze setting: 3000 rpm

0 %

[n]

100%

C0011

C0010

See chapter "Commissioning"

®

"Acceleration, deceleration, braking,
stopping"

20.

Set the acceleration time T

ir

(C0012)

Lenze setting: 5.00 s

f [ H z ]

f 2

C 0 0 1 1

f 1

0

t i r

t i f

T i r

T i f

t

T

ir

+ t

ir

@

C0011

f2 * f1

(see chapter "Commissioning"

®

"Acceleration, deceleration, braking,
stopping")

21.

Set the deceleration time T

if

(C0013)

Lenze setting: 5.00 s

T

if

+ t

if

@

C0011

f2 * f1

(see chapter "Commissioning"

®

"Acceleration, deceleration, braking,
stopping")

22.

If required, set the quick stop deceleration ramp
(C0105)
Lenze setting: 5.00 s

See chapter "Commissioning"

®

"Acceleration, deceleration, braking,
stopping"

23.

If required, adapt the fixed setpoints JOG.

See code table

A

JOG 1 (C0039/1)
Lenze setting: 1500 rpm

Activation:
X5/E3 = HIGH

B

Further fixed setpoints:
JOG 2 (C0039/2) ... JOG 15 (C0039/15)

24.

Ensure a powerfail−proof saving of the settings in
one of the four parameter sets (C0003)
Use C0003 = 1 to save the settings in parameter
set 1.

Code C0003 is the first code in the
menu "Setup V/f".
After switching on the DC 24 V supply
or mains connection, parameter set 1 is
automatically activated.
(see chapter "Parameter setting")

25.

Switch on the mains if the external DC 24 V supply
voltage is switched on only.

26.

Enable controller

misc009

59

28

X5

}

Terminal X5/28 = HIGH
(see chapter "Commissioning"

®"controller inhibit")

27.

Enter the setpoint

Analog setpoint
selection:
−10 ... +10 V via
potentiometer at X6/1
and X6/2

Fixed speed:
Activate JOG 1 with
X5/E3 = HIGH

JOG 1 is parameterised in C0039/1