Commissioning

Operating mode
V/f characteristic control

6

6.8
6.8.1

l

6.8−4

EDSVF9333V EN 6.2−04/2012

6.8.1

V/f characteristic control

The output voltage of the controller follows a defined characteristic. At low
output frequencies, the characteristic can be boosted. It can be adapted to
different load profiles.

ƒ Linear characteristic for drives with constant load torque over the

speed.

ƒ Quadratic characteristic for drives with quadratic load torque over the

speed:
– Quadratic V/f characteristics are preferably used in centrifugal pump

and fan drives. However, it must be checked whether your pump or
fan drive can be operated in this operating mode!

– If your pump or fan drive cannot be used for the operation with a

quadratic V/f characteristic, the linear V/f characteristic or vector
control mode must be used.

0

1

0

C0089

C0090

100 %

N

n
n

U

min

U

out

0

1

0

C0089

C0090

100 %

N

n
n

U

min

U

out

9300vec085

9300vec086

Fig. 6.8−3

Linear and square−law V/f characteristic

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0006

s

Op mode

5

Selection of the operating mode
for the motor control

1

vector ctrl

Vector control
without or with
speed feedback

In case of the first selection enter
the motor data and identify them
with C0148.

^
6.8−8

5

V / f

V/f characteristic
control

Commissioning without
identification of the motor data is
possible

l

Advantage of identification
with C0148: Improved smooth
running at low speeds

^
6.8−4

C0014 V/f charact.

0

Characteristic in the V/f
characteristic control mode

^
8.2−25

0

Linear

Linear V/f characteristic

1

square

Square V/f characteristic

C0015 Rated freq

50

10

{1 Hz}

5000 V/f−rated frequency

In C0015 you can set a base
frequency which differs from the
rated motor frequency (C0089)

l

Lenze setting: C0015 = C0089

l

Changing C0086 or C0089
overwrites the value in C0015

^