2 vector control, Vector control, Commissioning – Lenze EVF9333−xV User Manual

Page 218

Advertising
background image

Commissioning

Operating mode
Vector control

6

6.8
6.8.2

l

6.8−8

EDSVF9333V EN 6.2−04/2012

6.8.2

Vector control

Compared to the V/f characteristic control, the vector control serves to
achieve a considerably higher torque and lower current consumption in idle
state.

)

Note!

ƒ

The connected motor may be maximally two power classes
smaller than the motor assigned to the drive controller.

ƒ

The motor data identification is essential.

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0006

s

Op mode

5

Selection of the operating mode
for the motor control

1

vector ctrl

Vector control
without or with
speed feedback

In case of the first selection enter
the motor data and identify them
with C0148.

^
6.8−8

5

V / f

V/f characteristic
control

Commissioning without
identification of the motor data is
possible

l

Advantage of identification
with C0148: Improved smooth
running at low speeds

^
6.8−4

C0021 slipcomp

à

−20.00

{0.01 %}

20.00 Slip compensation

à

Change of C0086, C0087 or
C0089 sets C0021 to the
calculated rated slip of the
motor

l

When changing over to the
vector control mode, C0021 is
set to 0

^
6.11−1

^
8.2−25

^
8.2−48

C0075 Vp curr CTRL

0.20

0.00

{0.01 }

0.99 Gain of current controller

l

Vector control: gain of current
controller

l

V/f characteristic control:
maximum current controller

^
8.2−25

^
8.2−48

C0076 Tn curr CTRL

10.0

0.1

{0.1 ms}

2000.0 Integral−action time of current

controller

l

Vector control: integral−action
time of current controller

l

V/f characteristic control:
maximum current controller

l

C0076 = 2000 ms: current
controller is switched off

^
8.2−25

^
8.2−48

C0077 Ti field CTRL

4.0

0.3

{0.1 ms}

6000.0 Integral−action time of field

controller

l

Only active in case of vector
control with feedback

C0081

s

Mot power

à

0.01

{0.01 kW}

500.00 Rated motor power

à

Change of C0086 resets value
to factory setting

l

Change of C0081 sets C0086 =
0