Configuration, Code table – Lenze EVF9333−xV User Manual

Page 385

Advertising
background image

Configuration

Code table

8

8.5

l

8.5−37

EDSVF9333V EN 4.0−11/2007

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0594 MONIT SD6

3

0

TRIP

Activation of the motor
temperature monitoring with KTY
at X8

l

Use C0594 = 0 or 2 to activate
monitoring

l

In case of a short circuit or
interruption at X8/5 and X8/8
the fault message SD6 is
activated

l

Configuration of the response
when exceeding the motor
temperature
– Fixed operating temperature

in C0583

– Variable operating

temperature in C0584

^
6.6−10

See System
Manual
(extension)

2

Warning

3

Off

C0595 MONIT CE4

3

0

TRIP

Configuration of monitoring CE4,
BUS−OFF (system bus)

See System
Manual
(extension)

2

Warning

3

Off

C0596 NMAX limit

4000 0

{1 rpm}

36000 Configuration of monitoring N

max

,

maximum system speed exceeded

See System
Manual
(extension)

C0597 MONIT LP1

3

0

TRIP

Configuration of monitoring the
motor phases LP1

See System
Manual
(extension)

2

Warning

3

Off

C0598 MONIT SD5

3

0

TRIP

Configuration of monitoring SD5,
open circuit at analog input X6/1,
X6/2

See System
Manual
(extension)

2

Warning

3

Off

C0599 Limit LP1

5.0

1.0

{0.1 %}

10.0 Configuration of current limit LP1,

current limit value for monitoring
the motor phases in C0597

See System
Manual
(extension)

C0600 Function

1

0

OUT = IN1

Function selection, function block
ARIT2

See System
Manual
(extension)

1

OUT = IN1 + IN2

2

OUT = IN1 − IN2

3

OUT = IN1 * IN2

4

OUT = IN1 / IN2

5

OUT = IN1 / (100 − IN2)

C0601

s

^ Selection list 1

Configuration of analog input
signal, function block ARIT2

1 CFG: IN

1000 FIXED0%

ARIT2−IN1

2 CFG: IN

1000 FIXED0%

ARIT2−IN2

C0602

−199.99

{0.01 %}

199.99 Function block ARIT2

l

Display of the signals linked in
C0601

1 DIS: IN

ARIT2−IN1

2 DIS: IN

ARIT2−IN2