Commissioning, Selection of the correct operating mode – Lenze EVF9333−xV User Manual

Page 172

Advertising
background image

Commissioning

Selection of the correct operating mode

6

6.2

l

6.2−2

EDSVF9333V EN 6.2−04/2012

The following table helps you to find the correct operating mode for
standard applications:

ƒ C0006 = 5: V/f characteristic control with constant U

min

boost

ƒ C0006 = 1: vector control

Power range 0.37 ... 90 kW

Selection of the operating mode in C0006

Motor cable

shielded

£

50 m

unshielded

£

100 m

Motor cable

shielded

>

50 m

unshielded

>

100 m

recommen

ded

alternativ

ely

recommen

ded

alternativ

ely

Single drives

With constant load

1

5

5

With extremely alternating loads

1

5

5

With high starting duty

1

5

5

Positioning and infeed drives with high
dynamics

1

5

5

Rewinder with dancer

1

5

Unwinder with dancer

5

Pump and fan drives

1)

5

5

Three−phase AC reluctance motors

5

5

Three−phase AC sliding rotor motors

5

5

Three−phase AC motors with fixed
voltage/frequency characteristic

5

5

Group drives
(the resulting motor cable length I

res

) is

decisive

l

res

+ i

Ǹ

@ (l

1

) l

2

) AAA ) l

i

)

Identical motors and identical loads

1

5

5

Different motors and/or alternating loads

5

5

1)

For this application we recommend a quadratic voltage characteristic (C0014 = 1)

Operating modes
recommended for standard
applications

Advertising